Select Page

ABC PC Program

Start screen ABC PC program; ABC Server

  • Description of icons: 
    Code for user level
    Open the ABC control screen on the PC. The screens and operation are equal to the LCD

    Open the log data:

    • Charts
    • LCD screen
    Open the screen to configure data
    Open the screen to record and call up ‘preset’ basic settings
    Open configuration page of SMS module
    Open page to configure connection between C-Box and PC (only user 3)
    Open page to configure en check log data and settings.
    Save current settings. The technician can restore current settings after maintenance or test.
    Configure time at which settings will be automatically saved daily. In case of malfunction, failure or replacement of the C-Box, all settings of before the last ‘Backup’ can be restored directly.


     

    Type of connection PC with C-Box

    Status of connection

    Rx moving bars

    Tx

     

    Restore connection

Control Screen on PC

Control screen on PC with same layout as ABC touch screen.

Extras:

  • Screen can be reduced to 33% and enlarged to 150%.
  • Status specification of connection with C-Box
  • Extra navigation screens;
  • Click on ‘Navigation +’ to open 2 navigation screens.
  • You can open the desired page directly from every navigation screen.
  • Now you can easily open and compare 2 screens of random cells.

Click in the frame ‘Tools’ (above) on the  button to open the Log screen at the chosen time. The dotted line and   display the chosen time. All historic measurement and control data of that time are now visible on the screen. The time of the log screen can be changed by activating the dotted line and moving it, using the right mouse button.

Click on the  button in the left upper corner, to activate the measurement and control items of the screens and select them easily for the chart.

The ‘log screen’ is activated: . All measurement and control items, as well as ‘status’ and ‘alarm’ etc. have a red frame. Click on the frame to display this value in the chart. In the overview ‘Items’ the matching color of the value is displayed. Every quantity (°C, %, gr, ppm, status etc) has its own vertical axis.

  • The axis will be displayed when a measurent value with the relevant quantity has been chosen.
  • Use ‘shift+left mouse button’ to move the axis over the screen.
  • Each axis can be individually scaled using the scroll wheel of the mouse.
  • Use the  button to adjust all scales optimally to the various measurement values.

Control buttons for chart and LCD with log data.

Redraw AllChart will be supplemented with the latest log data
Fitt AllAll scales are adjusted for optimal display
LineOutAxisAll axis are replaced to start position
Clear all itemsAll chosen items will be cleared; empty screen.
Extra Axis smlFor mentioned quantity an extra axis is placed
MinMaxAVGThe minimum, maximum and average values will be displayed of the time zone as displayed on the screen.
Shift half time axesThe log display shifts half a page forward in time.
Plus 2 day smlThe log display shifts 2 days forward.
Plus 1 day smlThe log display shifts 1 day forward.
Min 1 day smlThe log display shifts 1 day backward.
Min 2 day smlThe log display shifts 2 days backward.
Min half tax smlThe log display shifts half a page backward in time.
Goto ddmm day smlGo directly to log data of this desired date.
1 day smlLog display on the screen of 1 day 0:00 to 23:59 hours
2 days smlLog display on the screen of 2 days
7 days smlLog display on the screen of 7 days
2 weeks smlLog display on the screen of 2 weeks
4 weeks smlLog display on the screen of 4 weeks
Fit X daysDisplay is adjusted to full days (0:00-23:59)
LCD smlDisplay of LCD on selected moment. All measurement and control values of that moment are visible
LCD sml playFrom the selected moment the LCD screen will shift automatically forward in time; measurement and control values will form a sequence. Changes in valve position, fans, colors, etc. are clearly visible on the LCD.
Log start from todayDisplay of the log starting today.
Log start from half year agoDisplay log of half a year
Log start from one year agoDisplay log of a year
Print smlPrint log data of displayed screen
Print setup smlChoose printer
Export to ExcelSelected data is opened in Excel and can be saved as an Excel file. (see next: ‘Procedure to open log data in Excel‘)

Procedure to open log data in Excel

Click the  button to open the following screen:

Procedure to open log data in Excel:

  • Choose the desired items from the selected items to export to Excel.
  • Choose the timeframe: ‘From date’ to ‘To date’
  • Choose the interval related to the size of the file (measurement per minute)

Choose the calculated value within the interval: Average, minimum, maximum

OK: Chosen measurement points are made visible with the configured interval in an Excel file